skip to Main Content

PRODUCTS

DISTRIBUTION TRANSFORMERS

Transformers with capacities ranging from 25 to 3150 kVA, and voltages up to 36 kV, in both three-phase and single-phase configurations.

Manufactured in strict compliance with applicable regulations, such as IEC 60076, RE-548, EN 50588 and UNE 21428, as well as corporate standards or customized specifications of our clients, we guarantee the delivery of reliable transformers, with quality being a constant objective at JARA .

With the approval of the main electricity companies – IBERDROLA, ENDESA, HC ENERGÍA and VIESGO –.

This production line covers transformers with capacities ranging from 25 to 3150 kVA, and voltages up to 36 kV, in both three-phase and single-phase configurations. All products are manufactured in strict compliance with applicable regulations, such as IEC 60076, RE-548, EN 50588 and UNE 21428, as well as corporate standards or customized specifications of our clients.

The option of using mineral oil or BIODEGRADABLE vegetable ester as insulating liquid is offered, the latter also being a type K liquid with a combustion point greater than 300ºC. Additionally, other liquids can be provided according to request, such as synthetic ester or silicone.

Characteristics:

  • Power: 25 kVA to 3150 kVA
  • High voltage: up to 36 kV (single-voltage or bi-voltage)
  • Frequency: 50 or 60 Hz
  • Low voltage: 420 V (options upon request: 242 V, 690 V, bi-voltage 420+242 V, etc.)
  • Connection group: Yzn11 or Dyn11 configurations up to 100 kVA, Dyn11 from 160 kVA
  • Liquid: mineral oil or type K liquids (silicone, natural or synthetic esters)
  • Expansion system: integral filling (options upon request: with expansion tank, with chamber)
  • Natural cooling: ONAN or KNAN
  • Standards: UNE 21428, RE 548, UNE-EN 60076 and technical specifications of companies

We guarantee the delivery of reliable transformers, with quality being a constant objective at JARA. We have approval from the main electricity companies such as IBERDROLA, ENDESA, HC ENERGÍA and VIESGO.

JARA operates under an integrated management system in accordance with the UNE-EN ISO 9001, UNE-EN ISO 14001 and UNE-EN ISO 45001 regulations, with the corresponding certifications.

JARA has two of its own laboratories equipped with cutting-edge technology and modern measurement equipment, regularly calibrated, where exhaustive tests are carried out on all transformers, following the guidelines established by the IEC 60076 standard, thus guaranteeing quality and optimal performance. of these.

INDIVIDUAL TESTS FOR EACH TRANSFORMER:

  • Accurate measurement of winding resistance.
  • Transformation ratio measurement and phase shift verification.
  • Measurement of short circuit impedance and load losses.
  • Measurement of losses and no-load current.
  • Carrying out applied voltage dielectric tests.
  • Carrying out dielectric tests of induced withstand voltage.
  • Carrying out pressure leak tests for transformers immersed in liquid (tightness test).
  • Measurement of the insulation resistance in direct current between each winding and ground, as well as between windings.

TYPE TESTS:

These tests are carried out periodically as part of regular internal verifications or according to agreements established with clients, always following the guidelines of the corresponding IEC 60076 standard.

  • Heating test, both of the liquid and the windings.
  • Full lightning impulse test.
  • Determination of the noise level.
  • Endurance test.
  • Test of the characteristics of painting.